Free Printable Reg 10(5) Refusal Log & NFPA 80 Checklist

Print either single-page clipboard sheet directly from your browser, or capture every inspection round offline on your phone in ClearGap.

Ready to Print

Select a sheet to print or inspect on site

On narrow phones, scroll horizontally inside each sheet frame—or tap Print to format cleanly onto A4 or US Letter paper.

UK Reg 10(5) Flat Entrance Door Refused-Access ("Best Endeavours") Log

England (>11m residential blocks): Quarterly checks on communal doors & annual "best endeavours" checks on flat entrance doors. Regulation 10(5) requires retaining timestamped evidence of access attempts, notices, and refusals. (Wales: FSO 2005 Art 17; Scotland: Fire (Scotland) Act 2005 — BS 9999 / BS 8214:2026 applies.)

Standard ClearGap Access Codes: No answer — card left · Written notice issued · Appointment missed · Refused verbal · Refused written · Locked / obstructed · Corridor-side external check only

Door / Flat ID Date & Time Access Status / Attempt Type Notice / Letter Ref Follow-Up Action / RP Escalation Initials
FD-14 / Flat 4B Sample Row No answer — card left Card #1 left under door Issue 7-day written appointment notice HS

US & Canada NFPA 80 Annual 13-Point Checklist & Wood vs Steel Clearance Chart

Mandatory annual swinging fire door verification (NFPA 80 Ch. 5, Sec. 5.2, CMS / Joint Commission / IFC / National Fire Code of Canada). Retain signed inspection records on site for at least 3 years.

Pt NFPA 80 Ch. 5 Mandatory Inspection Point Pass Criteria Summary P / F / N/A
01Labels Present, Legible & UnpaintedFire rating labels on door & frame readable, not painted over P   F
02No Open Holes or BreaksNo unsealed screw holes, splits, or rust-through on leaf/frame P   F
03Glazing, Vision Frames & BeadsListed fire-rated glass & vision kit intact and securely fastened P   F   N/A
04Door, Frame, Hinges & ThresholdAligned, anchored, noncombustible threshold in working order P   F
05No Missing or Broken PartsAll hinge screws, strikes, flush bolts & astragal parts intact P   F
06Pull-Side Clearances (Sec. 6.3.1.7 & 4.8.4)Within material tolerance table below (Head, Jambs, Meeting, Undercut) P   F
07Self-Closing Device OperationCloses active door completely from full open position P   F
08Coordinator Sequencing (Pairs)Inactive leaf closes completely before active leaf latches P   F   N/A
09Positive Self-Latching into StrikeLatch bolt engages strike cleanly from closer cycle without manual push P   F
10No Interfering Auxiliary HardwareNo wedges, kickdown stops, hooks, chains, or taped latches P   F
11No Unapproved Field ModificationsNo unauthorized cutouts, trimming, or prep voiding the listing P   F
12Edge Protection, Gasketing & NFPA 105 SealsIntumescent edges, astragals & smoke/draft seals intact P   F   N/A
13Signage (<5% Area & No Metal Fasteners)Adhesive-only signs covering <5% of door face; no screws/rivets P   F   N/A
NFPA 80 Door Assembly Type Head, Hinge, Lock & Meeting Stile (Sec. 6.3.1.7) Bottom Undercut (Sec. 4.8.4) Common Inspection Error
Steel / Hollow Metal Door 1/16" to 3/16" (nominal 1/8") ≤3/4" max (3/8" dutch / >38") Falsely failing 3/16" on steel doors
Wood Door (>20-min rating) ≤1/8" max ≤3/4" max (3/8" dutch / >38") Allowing 3/16" on 45/60/90-min wood doors
20-min Wood in Hollow Metal Frame 1/16" to 3/16" (nominal 1/8") ≤3/4" max (3/8" dutch / >38") Applying strict >20-min rule without checking listing