NFPA 80 Annual Swinging Fire Door Inspection Guide (US & Canada)
Complete reference for NFPA 80 Chapter 5 annual 13-point checks, pull-side Steel vs Wood perimeter clearances, standard vs dutch door undercuts, and Authority Having Jurisdiction (AHJ) record retention.
1. Pull-Side Perimeter & Bottom Clearances (Sec. 6.3.1.7 & 4.8.4)
Always measure NFPA 80 perimeter clearances on the pull side of the closed door assembly. Applying steel tolerances to high-rated wood doors — or wrongly failing 3/16" on hollow metal doors — is one of the most frequent field errors during healthcare and commercial inspections.
| Door Assembly Material / Frame | Head, Hinge, Lock & Meeting Stile (Sec. 6.3.1.7) | Bottom Undercut (Sec. 4.8.4) | Field Inspection Note |
|---|---|---|---|
| Steel / Hollow Metal Door | 1/16" to 3/16" (1/8" ± 1/16") | ≤3/4" max | <1/16" flags binding advisory; 3/16" passes. |
| Wood Door (>20-min rating) | ≤1/8" max | ≤3/4" max | 3/16" fails on 45, 60, and 90-min wood doors. |
| 20-min Wood in Hollow Metal Frame | 1/16" to 3/16" (1/8" ± 1/16") | ≤3/4" max | Permits 1/8" ± 1/16" per NFPA 80 Sec. 6.3.1.7. |
| Dutch Doors / Door Bottom >38" Above Floor | Per door material above | ≤3/8" max | Applies to upper/lower dutch door split and elevated hatches. |
2. The 13 Mandatory NFPA 80 Ch. 5 Swinging Fire Door Inspection Points
Under NFPA 80 Section 5.2, every swinging fire door assembly must be inspected and tested annually against all 13 points below (built directly into ClearGap's US & Canada preset):
| Pt | Mandatory Check Point | Pass Criteria & Common Defects |
|---|---|---|
| 01 | Labels Present, Legible & Unpainted | Both door and frame certification labels are intact, readable, and not painted over or obscured. |
| 02 | No Open Holes or Breaks | No unsealed screw holes, splits, or rust-through on leaf or frame (fill unused holes per Sec. 5.2.3.5.2). |
| 03 | Glazing, Vision Frames & Beads | Listed fire-protection-rated glass and vision-lite frames intact and tightly fastened (N/A on solid doors). |
| 04 | Door, Frame, Hinges & Threshold | Door, frame, listed ball-bearing hinges, and noncombustible threshold are aligned and securely anchored. |
| 05 | No Missing or Broken Parts | No missing hinge screws, strike plates, flush bolts, or astragal parts. |
| 06 | Pull-Side Clearances (Sec. 6.3.1.7 & 4.8.4) | Within material tolerance table above (1/16"–3/16" steel / 20-min HM; ≤1/8" wood >20-min; ≤3/4" or ≤3/8" undercut). |
| 07 | Self-Closing Device Operation | Active door closes completely when operated from the full open position without assistance. |
| 08 | Coordinator Sequencing (Pairs) | Where fitted, coordinator and carry bar ensure inactive leaf closes before active leaf (N/A on singles). |
| 09 | Positive Self-Latching into Strike | Latch bolt positively engages the strike on closing without manual push; latches never taped or dogged. |
| 10 | No Interfering Auxiliary Hardware | No door wedges, kickdown stops, hooks, non-listed chains, or slide bolts interfering with closure. |
| 11 | No Unapproved Field Modifications | No unauthorized cutouts, field welding, or excessive trimming that voids the door or frame listing. |
| 12 | Edge Protection, Gasketing & NFPA 105 Seals | Intumescent edges, meeting-edge astragals, and UL 1784 / NFPA 105 smoke & draft-control seals intact. |
| 13 | Signage (<5% Area & No Metal Fasteners) | Attached informational signs cover <5% of door face and use adhesive only — no screws, nails, or rivets. |
3. 3-Year Record Retention & Qualified Person Duty
NFPA 80 Section 5.2.2 requires written or electronic inspection records signed by the qualified inspector to be kept available for AHJ audit for at least 3 years. ClearGap generates compact Defect-Only Compliance PDFs, remedial works schedules (Excel), Client Handover Packs (PDF + remedial schedule + photo folder ZIP), and phone-to-phone backup archives with no cloud portal fees.
4. NFPA 80 Frequently Asked Questions
What is the NFPA 80 gap tolerance for steel vs wood fire doors?
Under NFPA 80 Section 6.3.1.7 measured on the pull side, steel or hollow metal fire doors and 20-minute wood doors in hollow metal frames allow 1/16" to 3/16" (1/8" ± 1/16") along the head, jambs, and meeting edge. Wood doors rated over 20 minutes (45, 60, or 90-minute) are capped at ≤1/8" maximum.
What is the maximum bottom undercut allowed under NFPA 80?
Under NFPA 80 Section 4.8.4, standard bottom clearance between the door bottom and finished floor or threshold is ≤3/4" maximum. For dutch doors or door bottoms more than 38 inches above the floor, the maximum clearance is ≤3/8".
How long must NFPA 80 annual fire door inspection records be retained?
NFPA 80 requires signed inspection records to be retained on site for review by the Authority Having Jurisdiction (AHJ) for at least 3 years.
Are screws or rivets allowed for informational signs on NFPA 80 fire doors?
No. NFPA 80 limits informational signage to <5% of total door face area applied with adhesive only — mechanical metal fasteners (screws, nails, or rivets) puncture the door face and constitute a point-13 failure.