Fire Safety (England) Regulations 2022 Regulation 10 Guide
Routine inspection cadences for residential buildings over 11 metres, the 7-point Regulation 10 check, simplified Reg 10 visual mode, and defensible Regulation 10(5) "best endeavours" refusal records.
1. Who Is Responsible & Inspection Frequencies
In England, the Responsible Person (RP) — typically the freeholder, Resident Management Company (RMC), managing agent, or housing provider — must implement routine fire door checks on residential buildings containing two or more domestic premises where the top storey is above 11 metres:
| Door Location | Required Frequency | Statutory Requirement |
|---|---|---|
| Communal Fire Doors Stairwell doors, lobby doors, cross-corridor doors, riser/plant cupboards |
Every 3 months (Quarterly) |
Check all fire doors in communal parts as part of routine quarterly rounds. |
| Flat Entrance Doors Doors leading from individual dwellings into common hallways or stairwells |
Every 12 months (Annually) |
Use "best endeavours" to inspect all flat entrance doors; retain Reg 10(5) access & refusal evidence where entry is not gained. |
2. What a Regulation 10 Routine Check Covers (7 Practical Points)
Regulation 10 routine checks focus on visible condition, self-closing performance, seals, and visual clearance checks without requiring destructive testing. ClearGap's UK Reg 10 preset uses a simplified Reg 10 visual mode by default (with optional tap-to-expand gauge schematic) across 7 crisp checks:
- Self-Closing Device & Positive Latching: Confirm the closer closes the door smoothly from full open and ~75 mm without slamming, engages the latch cleanly, and is not wedged or propped open.
- Intumescent Strips & Cold-Smoke Seals: Check seals are present, continuous around frame or leaf edges, undamaged, and never painted over.
- Door Leaf, Frame & Fire-Stopping: Check for holes, cracks, severe warping, unapproved letterplates/viewers/cat flaps, and damaged frame-to-wall fire-stopping.
- Perimeter & Threshold Gaps: Visually inspect clearances and optionally expand the gauge schematic for perimeter (2–4 mm pass) and threshold (≤3 mm or functioning drop-seal on smoke doors; ≤8–10 mm fire-only) measurements. See our BS 8214:2026 Gap Tolerances Guide.
- Hinges, Lock & Essential Hardware: Confirm at least 3 fire-rated hinges with all steel screws tight, no dark metal swarf wear, and smooth latch operation.
- Fire-Rated Glazing & Beads: Where glazed, verify intact rated glass and tightly fixed glazing beads (N/A on solid flat entrance doors).
- Mandatory Fire Door Signage: Confirm blue circular BS 5499 / ISO 7010 signs on both faces of communal and cupboard doors (N/A on flat entrance doors).
3. Regulation 10(5) "Best Endeavours" & Refused-Access Logging
Inspectors and managing agents cannot force entry into an occupied flat. Instead, Regulation 10(5) requires retaining clear records showing that reasonable, repeated steps ("best endeavours") were taken to gain access and that unresolved refusals were escalated to the Responsible Person.
ClearGap builds these seven timestamped access codes directly into the inspection bar (alongside closed-door corridor photo evidence):
| ClearGap Access Code | Access Status | Recommended Reg 10(5) Follow-Up |
|---|---|---|
| No answer on visit — card left | No Answer | Record date/time of physical door knock and leave appointment card. |
| Written appointment notice issued | No Answer | Log date and method (letter, email, SMS) offering multiple visit windows. |
| Pre-arranged appointment missed | No Answer | Timestamp missed attendance and issue follow-up written notice. |
| Resident refused access at door | Refused Access | Do not force entry; note refusal calmly and escalate to Responsible Person. |
| Resident refused in writing | Refused Access | Archive email/letter refusal alongside earlier appointment notices. |
| Door locked / key unavailable / obstructed | Locked | Note physical access barrier and notify managing agent for riser/cupboard key. |
| Corridor-side external check only | Refused Access | Document external face defects only; never mark defect-free without internal closer/hinge check. |
4. Regulation 10 Frequently Asked Questions
Which buildings fall under Regulation 10 of the Fire Safety (England) Regulations 2022?
Regulation 10 applies to all multi-occupied residential buildings in England over 11 metres in height (typically five storeys or more) with two or more domestic premises. Under Regulation 10(2), information on the importance of fire doors must also be provided to residents in all multi-occupied residential buildings regardless of height.
How often must communal and flat entrance fire doors be checked under Reg 10?
The Responsible Person must undertake checks of all fire doors in communal areas every three months (quarterly), and use best endeavours to undertake checks of all flat entrance doors opening onto common parts at least once every 12 months (annually).
What evidence should a Regulation 10(5) best-endeavours refusal log record?
Retain timestamped logs of initial door knocks, written appointment notices, missed pre-arranged slots, verbal or written resident refusals, and escalation notes sent to the Responsible Person. ClearGap exports all refusal records directly into your PDF report, remedial works schedule (Excel), and Client Handover Pack.
Can a corridor-side visual check count as a full flat entrance door pass?
No. A corridor-side visual check cannot verify internal closer performance or hinge-side intumescent strips. Record it as partial corridor-side access only and retain best-endeavours follow-up attempts.